Pneumatic Regulators

A pressure regulator reduces an unregulated high input pressure to a regulated lower output pressure. Its primary function is to maintain the regulated output pressure under flowing and non-flowing conditions.

Fairchild manufactures a complete line of precision pneumatic regulators including positive pressure, back pressure and vacuum models. Quality engineering and manufacturing excellence assures that our pressure regulators meet all the requirements of a precision device.

Our large selection of pressure ranges and flow capacities lets you select the models that meet your needs for instrument or general industrial control applications.

Flow Capacity:
SCFM (m3/HR) Supply =100 psig
Exhaust Capacity:
SCFM (m3/HR) Downstream pressure
5 psig above 20 psig set point
Sensitivity:
Inch/WC (cm)
Supply
Pressure Var:

PSIG (kPa) For Supply Change:
Supply
Pressure Max:

PSIG (kPa)
Dimensions (Approx):
Inches (mm)
Range PSIG (kPa)Pipe Size NPT
10 Precision Regulator10 Precision Regulator40 (68)5.5 (9.4)0.125 (0.32)<0.1 (<0.7)
100 psig
500 (3500)Dia. 3 H 6 1/2
(Dia. 76 H 165)
0-2 (0-15),
0-10 (0-70),
1-20 (0-150),
0.5-30 (3-200),
1-60 (10-400),
2-150 (15-1000),
3-200 (20-1500),
5-300 (35-2100),
5-400 (35-2800)
1/4”, 3/8”, 1/2”
16 Vacuum Regulator16 Vacuum Regulator2.5 (4) @ 29”
Vacuum w/inlet port open 40 (68)
Positive Flow
5.5 (9.4)0.50 (1.27)<0.1 (<0.7)
100 psig
250 (1700)Dia. 3 H 8
(Dia. 76 H 203)
Vacuum-2 (Vacuum-15),
Vacuum-10
(Vacuum-70),
Vacuum-30
(Vacuum-200),
Vacuum-100
(Vacuum-700),
Vacuum-150
(Vacuum-1000)
1/4”, 3/8”, 1/2”
30 Compact Precision Regulator30 Compact Precision Regulator40 (68)2.0 (3.4)0.25 (0.63)<0.2 (1.4)
100 psig
250 (1700)2 1/2 x 1 3/4 x 5 1/4
(57 x 44 x 133)
0-2 (0-15),
0-10 (0-70),
0.5-30 (3-200),
1-60 (10-400),
2-100 (15-700)
1/4”, 3/8”
50 Mini Precision Regulator50 Mini Precision Regulator10 (17.0)
Supply =120 psig
2.0 (3.4)
Downstream pressure is 15 psig
5.0 (12.7)<0.1 (<0.7)
10 psig
150 (1000)1.84 x 3.73
(46.7 x 94.7)
0-10 (0-70)
.5-30 (3-200)
1-60 (7-400)
2-100 (15-700)
1/4”
63 Filter Regulator63 Filter Regulator25 (42.5)0.8 (1.36)1.0 (2.54)<1.25 (<9)
100 psig
250 (1700)2 x 3 x 7 3/4
(76 x 76 x 197)
0.5-30 (3-200),
1-60 (10-400),
2-120 (15-800)
1/4”
64A, 65A Filter Regulator64A, 65A Filter Regulator22 (37.4)1.0 (1.7)1.0 (2.54)<0.1 (<0.7)
25 psig
300 (2100)3 x 3 x 9
(76 x 76 x 229)
0.5-30 (3-200),
1-60 (10-400),
2-120 (15-800)
1/4”
66 Stainless Regulator66 Stainless Regulator17 (28.9)1.0 (1.7)1.0 (2.54)<0.1 (<0.7)
25 psig
500 (3500)Dia. 3 x 6 1/4
Dia. (76 x 159)
0-10 (0-70),
0.5-30 (3-200),
1-60 (10-400),
2-100 (15-700),
2-150 (15-1000)
1/4”
70B Sub Miniature Regulator70B Sub Miniature Regulator2.5 (4.25)0.28 (0.48)N/A<0.05 (<0.35)
5 psig
250 (1700)Dia. 7/8 H 3 3/16
(Dia. 22 H 81)
0-5 (0-35),
0-15 (0-100),
0.5-30 (3-200),
1-60 (10-400),
2-100 (15-700)
1/16”
81 Hight Flow Precision Two-Stage Regulator81 Hight Flow Precision Two-Stage Regulator50 (85)5.5 (9.4)<0.1 (<0.254)<0.2 (<1.4)
100 psig
2 & 5 psig range
100 (700)
All other ranges
150 (1000)
Dia. 3 H 6 1/4
(Dia. 76 H 159)
0-2 (0-14),
0-5 (0-35),
0-20 (0-150),
0.5-60 (3.5-400),
0.5-100 (3.5-700)
1/4”
100 High Flow Regulator100 High Flow Regulator1500 (2550)44 (75)0.5 (1.27)<0.5 (<3.5)
100 psig
250 (1700)Dia. 5 1/2 H 11 1/4
(Dia. 133 H 286)
0-10 (0-70),
0.5-30 (3-200),
1-60 (10-400),
2-100 (15-700),
2-150 (15-1000)
1”, 1 1/2”
1000 No Bleed Design Regulator1000 No Bleed Design Regulator50 (85)8 (13.6)0.5 (1.27)<0.1 (<0.7)
100 psig
250 (1700)2 1/8 x 2 1/8 x 5
(54 x 54 x 127)
0.5-10 (3.5-70),
0.5-30(3.5-200),
1-60 (7-400),
2-150 (15-1000)
1/4”, 3/8”
1600A High Flow Vacuum Reg.1600A High Flow Vacuum Reg.28 (48) @ 29”
Vacuum w/inlet port open
150 (255)
Positive Flow
20 (34)1.0 (2.54)<0.1 (<0.7)
100 psig
250 (1700)Dia. 4 1/2 H 9 1/2
(114 x 241)
Vacuum-10 (Vacuum-70),
Vacuum-30 (Vacuum-200),
Vacuum-150 (Vacuum-1000)
3/8” x 1/2” x 3/4”
2400 Motorized Lock-in Position Reg.2400 Motorized Lock-in Position Reg.Up to 50 (85)5.5 (9.4)<0.1 to 0.125
(0.25 to 0.32)
<0.1 (<0.7)up to 500 (3500)Dia. 4 1/2 H 12 5/8
(114 x 321)
Numerous
(See catalog pages)
1/4” x 3/8” x 1/2”
4000A High Flow No Bleed Design Reg.4000A High Flow No Bleed Design Reg.150 (255)40 (65.2)0.5 (1.27)<0.1 (<0.7)
100 psig
250 (1700)Dia. 4 1/2 H 8
(Dia. 114 x 203)
0.5-10 (3.5-70),
0.5-30 (3.5-200),
1-60 (7-400),
2-150 (14-1000),
5-250 (35-1700)
3/8”, 1/2”, 3/4”

Pneumatic Volume Boosters

A pneumatic air volume booster reproduce a low flow control signal with a higher regulated flow output pressure. It uses an unregulated input pressure to maintain a regulated output pressure under flowing and non-flowing conditions.

Fairchild volume boosters meet all the requirements of a precision device including:

  • Accuracy
  • Sensitivity
  • Fast response
  • Stability
  • Drift-free settings
  • Low output droop
  • Supply pressure immunity
  • High forward and exhaust flow capacity

The regulated output of a pneumatic air volume booster can be any of the following:

  • A direct reproduction of the pneumatic control signal
  • A multiple of the pneumatic control signal
  • A fraction of the pneumatic control signal

Our large selection of pressure ranges and flow capacities let you select the models that meet your needs for instrument or general industrial control applications.

Flow Capacity:
SCFM (m3/HR)
Supply =100 psig
Exhaust Capacity:
SCFM (m3/HR)
Downstream pressure 5 psig
above 20 psig set point
Sensitivity:
Inch/WC (cm)
Supply
Pressure Var:

PSIG (kPa) For Supply Pressure
Change = 100 psig
Supply
Pressure (Max):

PSIG (kPa)
Max Signal/Output Pressure:
PSIG (kPa)
Dimensions (Approx):
Inches (mm)
Ratio AvailablePipe Size
20 Precision Booster20 Precision Booster45 (76.5)7.5 to 11
(12.8 and 18.7)
Varies with ratio
.25 to 1.50
(.64 to 3.8)
Varies with ratio
0.1 to 0.60
(0.7 to 4.0)
Varies with ratio
250 (1700)Varies
(see Catalog)
Dia. 3 H 4 1/4
(Dia. 76 H 114)
1:1, 1:2, 1:3, 2:1, 3:1
1:4, 4:1, 1:5, 5:1, 1:6
1/4”, 3/8”
200 High Flow Booster200 High Flow Booster1500 (2550)65 (110.5)1.0 (2.54)<0.5 (<3.5)250 (1700)150 (1000)Dia. 5 1/2 H 7 7/8
(Dia. 140 H 200)
1:11”, 1 1/2”
200XLR High Forward & Exhaust Flow Booster200XLR High Forward & Exhaust Flow Booster1500 (2550)325 (552.5)1.0 (2.54)<0.5 (<3.5)250 (1700)150 (1000)9 1/2 x 5 1/2 x 9 3/4
(241 x 140 x 248)
1:11 1/2”
2000 No Bleed Design Booster2000 No Bleed Design Booster40 (68)16 (27.2)<1.0 (2.54)<0.1 (<0.7)250 (1700)150 (1000)2 x 2 x 3 1/4
(54 x 54 x 83)
1:1, 1:1.61/4” 3/8”
4500A High Flow No Bleed Design Booster4500A High Flow No Bleed Design Booster150 (255)40 (65.2)1.0 to 3.0
2.54 to 7.62)
Varies with ratio
<0.1 to 0.3
(0.7 to 2.1)
Varies with ratio
250 (1700)Varies
(see Catalog)
Dia. 4 1/2 5 1/4
(Dia. 114 H 133)
1:1, 1:2, 1:3, 2:1, 3:13/8” 1/2” 3/4”

Electro-Pneumatic

Max Flow Capacity:
SCFM (m3/HR)
Output Pressure:
PSIG (kPa)
Exhaust Capacity:
SCFM (m3/HR)
Downstream pressure 5 psig
above 9 psig setpoint
Max Air Consumption:
SCFH (m3/HR)
Accuracy: % FSRepeatability: % FSSupply Pressure:
PSIG (kPa)
Supply Voltage:
DC
Input SignalPipe SizeUnderwriting Group Approvals:Dimensions (Aprx.) Inches (mm)
T1750 High Pressure I/P, E/PT1750 High Pressure I/P, E/P1000 (1699.2)
Supply = 600 psig
300-750
(2068-5171)
190 (322.8)
@ downstream
presssure
300 psig
0 @ steady state±0.5 Independent Linearity<0.11000 (7000) Miximum24 VDC4-20 mA, 0-10 VDC1/4", 3/8",1/2", 3/4”CE3x4 7/64 x 4 15/16
(76 x 37.7 x125.3)
T5700 High Flow Voice Coil I/P, E/PT5700 High Flow Voice Coil I/P, E/P47 (79.9) Supply =120 psig3-15 (20-100)< 9 (15.3)3 (.08)±0.5 Independent Linearity<0.118-150 (120-1000)Signal Powered41-250VmDAC, ,1 10-950VDmCA1/4”CEDia. 3 H 6 1/2
(Dia. 76 H 165)
T6000 Voice Coil I/P, E/PT6000 Voice Coil I/P, E/P9 (15.3) Supply =120 psig3-15, 0-120
(20-100), (0-800)
6 ranges
2 (3.4)5.0 to 17.0
(0.14) to (0.48)
Varies with model
0.5 to 1.01.0 Independent Linearity0.25 to <1.020-150
(150-1000)
Signal Powered4-20 mA, 10-50 mA 0-5 VDC, 0-10 VDC, 1-5 VDC, 1-9 VDC1/4”F, C, E, CE1 1/2 x 3 1/8 x 3 3/4
(38 x 79 x 95)
T7800 Piezo Ceramic I/P, E/PT7800 Piezo Ceramic I/P, E/P9 (15.3)
Supply =120 psig
3-15, 0-120
(20-100), (0-800)
6 ranges
2 (3.4)5.5 to 15.0
(0.16) to (0.42)
Varies with model
±0.15 (typical)<0.120-150
(150-1000)
Current Input
Signal Powered
Voltage Input
7.2-30 VDC
4-20 mA DC,
0-10 VDC,
1-9 VDC
1-5, 0-5 VDC Limited Availability
1/4”F, C, E, CE1 1/2 x 3 1/8 x 3 3/4
(38 x 79 x 95)
TXI780 Exploision-Proof I/P, E/PTXI780 Exploision-Proof I/P, E/P9 (15.3)
Supply =120 psig
3-15, 3-27, 6-30
(20-100), (20-180),
(40-200)
2 (3.4)13.5 (0.38)±0.15 (typical)<0.120-120
(150-800)
Maximum
Signal Powered4-20 mA1/4”A, F, C, E, CE3 11/16 x 3 13/16 x 4 5/8
(94 x 97 x 117.5)
T7900 High Flow Digital I/P, E/PT7900 High Flow Digital I/P, E/P100 (17.0)
Supply =100 psig
0-30, 0-75, 0-150
(0-200), (0-500),
(0-1000)
50 (85)0 @ steady state± 0.5<0.1200 (1400) Maximum24 VDC4-20 mA, 0-10 VDC
DeviceNet
1/4”, 3/8”, 1/2”CE3 x 3 1/8 x 7 3/4
(76 x 79 x 197)
T7950 Digital I/P, E/PT7950 Digital I/P, E/P11 (18.7)
Supply =150 psig
3-15, 0-120
(20-100), (0-800)
6 ranges
2 (3.4)0 @ steady state± 0.5<0.1150 (1000)24 VDC4-20 mA, 0-10 VDC
DeviceNet
1/4”CE1 1/2 x 3 x 8 1/2
(38 x 76 x 216)